Formula and method
Worked example
400 V, 10 A, PF 0.85: S ≈ 6.928 kVA, P ≈ 5.889 kW, Q ≈ 3.650 kvar.
Assumptions and limits
- For a 400 V system, enter 400 V between phases, rather than approximately 230 V to neutral. Results already include all three phases.
- Motor electrical input differs from shaft output: shaft output equals active electrical input multiplied by motor efficiency. This calculator does not estimate shaft power.
- VFDs, rectifiers, significant harmonics and unbalanced loads require suitable phase-by-phase measurements; this cos φ model does not replace true-power analysis.
Frequently asked questions
Why does the formula use √3?
Balanced three-phase power is three times per-phase power. Expressing it with line-to-line voltage gives the √3 factor.
What happens at a power factor of 1?
In the sinusoidal model, φ is 0°, reactive power is zero and active power equals apparent power numerically.